The ECM-1240 consists of two type of power monitoring inputs:
- CH1 & CH2 Inputs
- AUXILIARY Inputs (AUX1 to AUX 5)
|
|
CH1 & CH2 INPUTS
|
Measurement
|
Measures "True" or "Real" power based on current and voltage oversampling. The measurements take power factor into account.
Uses automatic gain scaling.
Also measures voltage and current seperately.
|
Input Signal:
|
Requires a voltage signal proportional to the input current.
333mV Full-Scale
NOTE: The input signal MUST be galvanicaly isolated from the powerline.
|
Input Impedance:
|
20K ohm using the COM and SINGLE terminals.
40K ohm using the COM and DUAL terminals
|
Max Power Measurement:
|
65,535 Kilowatt per channel. (CH1 & CH2) |
Max Current Measurement:
|
546 Amps based on 120V line voltage |
Accuracy:
|
Typically +/- 1% plus CT & PT accuracy. |
CT Compatibility:
|
Specifically designed for Brultech's "SPLIT" CTs available for 60A, 100A, 170A, 200A and 400A.
Also compatible with Brultech's Micro CTs with the inclusion of a burden resistor.
Compatible with any CT having 333mV Full Scale and phase error < 2 degrees
CT scaling is configurable to suit the type of CT used.
|
Energy Measurement:
|
Kilowatt-Hour is calculated based on all samples and is updated every second. |
Kilowatt-Hour (kWh) Resolution:
|
1 Watt-Second |
Net Metering:
|
Measures directional energy to provide consumed/generated values crucial for net metering applications. |
Power Resolution:
|
1 Watt |
|
AUX1 to AUX5 INPUTS
|
Measurement
|
Measures "True" or "Real" power based on current and voltage oversampling. The measurements take power factor into account. |
Input Signal
(AUX1 to AUX4):
|
Requires a current signal proportional to the input current.
52.46 mA FS
|
|
Power Metering:
Requires a current signal proportional to the input current.
52.46 mA FS with external 20 ohm resistor accross the COM and AUX5 terminals.
Pulse Counting:
Dry contact closure between the GND and AUX5 terminals. Contacts must be isolated from outside voltage sources or electrical ground.
|
|
|
COMMUNICATION
|
The ECM-1240 has the following communications ports:
- One RS-232 Port
- Optional wireless communication port
|
|
RS-232 Port
|
Connection:
|
Terminal strip connection: Common, Transmit, Receive |
Baud:
|
19,200 Baud (8N1) |
|
|
|
Wireless Communication (optional)
|
|
NOTE: Wireless communication is not WiFi . |
Frequency:
|
2.4 GHz |
Network Type:
|
ZigBee mesh network |
Transmit Power
|
2mW |
Antenna:
|
Internal wire whip or External 2.1dBi swivel antenna |
Sensitivity:
|
-96 dBm |
Range:
|
133 Feet* indoors, 400 Feet outdoors (line of sight)
* Range is largely affected by the number of walls the RF signal must travel. The wall density, material and outside interference also affects the range.
|
Interference Immunity:
|
DSSS (Direct Sequence Spread Spectrum) |
Baud:
|
19,200 Baud |
Hardware:
|
Digi International's XBee module (www.digi.com) |
Firmware:
|
Digi International's ZB firmware. (www.digi.com) |
|
|
|
Data Communication
|
Configuration:
|
Uses proprietary binary commands for initial configuration and setup. |
Data Output:
|
Choice of three packet format types:
- Binary (standard format)
- ASCII
- HTTP (requires EtherPort or EtherBee gateway)
|
Binary Packets:
|
The is the most common mode of operation. The packet data is configured for efficient data transfer using a proprietary protocol.
Packet Send Frequency: 1 second to 255 second
|
ASCII Packets:
|
This format is now offered with newer versions of the firmware to simplify the development of custom software.
Packet Send Frequency: 2 second to 255 second
|
HTTP Packets:
|
Using this format along with and EtherPort or EtherBee gateway, packets may be forwarded directly to a web server for processing using HTML, PHP, ASP or other web based languages.
Packet Send Frequency: 10 second to 255 second.
|
Triggered Packet Send:
|
Immediate packet send (within one second) for power changes of a defined amount.
Trigger Threshold: 10W to 65kW
*Does not apply to HTTP mode
|